Danfoss VLT FC51 inverter fault code query
Jun 16,2023 | simplybuy industrial
Please select the fault code number according to the Danfoss inverter panel prompts to inquire:
FC51 series
Fault code: 2
Fault phenomenon: disconnection fault
Fault causes and countermeasures: The signal on terminal 53 or 60 is lower than 50% of the setting in 6-10 terminal 535 low voltage, 6-12 terminal 53 low current or 6-22 terminal 54 low current
Fault code: 4
Fault phenomenon: main power supply phase loss
Fault cause and countermeasures: The power supply side lacks phase, or the voltage is seriously unbalanced. Check the vehicle power supply voltage. Check the supply voltage and current of the inverter.
Fault code: 7
Fault phenomenon: DC circuit overvoltage
Causes and countermeasures of the fault: the voltage of the intermediate circuit exceeds the limit
Fault code: 8
Fault phenomenon: DC circuit undervoltage
Fault causes and countermeasures: The intermediate circuit voltage is lower than the "low voltage warning" limit.
Fault code: 9
Fault phenomenon: Inverter overload
Causes of failure and countermeasures: The load exceeding 100% lasted for too long. Check whether the output current of the inverter reaches the rated current.
Fault code: 10
Fault phenomenon: Motor ETR overheating
Cause of failure and countermeasures: The load of more than 100% lasts for too long, so that the motor becomes overheated. Check whether the output current of the inverter reaches the rated current
Fault code: 11
Fault phenomenon: The temperature of the motor thermistor is too high
Cause of failure: The thermistor or the connection of the thermistor is disconnected. Check the thermistor
Fault code: 12
Fault phenomenon: torque limit
Fault reasons and countermeasures: The torque exceeds the setting value in parameter 4-16 or 4-17.
Fault code: 13
Fault phenomenon: overcurrent
Fault cause and countermeasure: Exceeded the peak current limit of the inverter.
Fault code: 14
Fault phenomenon: ground fault
Fault reasons and countermeasures: The output phase discharges to the ground. Use a megohmmeter to test the insulation of the output power supply to ground.
Fault code: 16
Symptom: short circuit
Fault cause and countermeasure: Short circuit occurs in the motor or motor terminals.
Fault code: 17
Symptom: control word timeout
Fault reasons and countermeasures: No information is sent to the inverter. Check communication lines
Fault code: 25
Symptom: Brake resistor short circuit
Fault causes and countermeasures: The braking resistor is short-circuited, thereby disconnecting the braking function.
Fault code: 27
Symptom: Brake chopper short circuit
Fault causes and countermeasures: The braking transistor is short-circuited, thereby disconnecting the braking function.
Fault code: 28
Symptom: Brake check
Fault reasons and countermeasures: The brake resistor is not connected, or it cannot work.
Fault code: 29
Fault phenomenon: power card temperature
Causes of failure and countermeasures: reach the cut-off temperature of the heat sink.
Fault code: 30
Fault phenomenon: motor lacks U phase
Fault cause and countermeasure: Motor U phase is missing, please check this phase.
Fault code: 31
Fault phenomenon: the motor lacks V phase
Cause of failure: The V phase of the motor is missing, please check this phase.
Fault code: 32
Fault phenomenon: motor lacks W phase
Fault cause and countermeasure: Motor W phase is missing, please check this phase.
Fault code: 38
Symptom: internal failure
Cause of failure: Please contact the supplier at the time of purchase
Fault code: 44
Fault phenomenon: ground fault
Fault reasons and countermeasures: The output phase discharges to the ground.
Fault code: 47
Fault phenomenon: control voltage fault
Cause of failure: 24V DC may be overloaded.
Fault code: 51
Symptom: ama checks unom and inom
Cause of failure: wrong setting of motor voltage or motor current.
Fault code: 52
Symptom: ama inom is too low
Cause of failure: The motor current is too low, please check the relevant settings.
Fault code: 59
Fault phenomenon: current limit
Fault causes and countermeasures: vlt is overloaded.
Fault code: 63
Fault phenomenon: The mechanical brake is too low.
Fault causes and countermeasures: The actual motor current has not exceeded the "brake release" current during the "start delay" period.
Fault code: 80
Fault phenomenon: Inverter initialization
Cause of failure: The settings of all parameters are initialized to the default settings
Fault code: 84
Fault phenomenon: The connection between the inverter and 1cp is lost
Cause of failure: No communication between lcp and inverter
Fault code: 86
Symptom: Replication fails
Cause of failure: An error occurred when copying between the inverter and lcp
Fault code: 87
Symptom: lcp data is invalid
Cause of failure: This error occurs when copying from lcp if lcp contains wrong data or no data is uploaded to lcp.
Fault code: 88
Symptom: lcp data is not compatible
Cause of failure: This error occurs when copying from lcp if data is moved between drives with very different software versions
Fault code: 89
Symptom: The parameter is read-only
Cause of failure and countermeasures: This error occurs when trying to write a read-only parameter.
Fault code: 90
Symptom: The parameter database is busy
Cause of failure: lcp and rs485 connections try to update parameters at the same time.
Fault code: 91
Symptom: The parameter value is invalid in this mode
Cause of failure: This error occurs when trying to write an illegal value to a parameter
Fault code: 92
Symptom: The parameter value exceeds the minimum/maximum limit
Failure reason: This error occurs when trying to set a value out of range.